Motion sensor with bypass switch?












1














I wish to have a motion sensor on the lights in my garage, but I also want to have an override switch that works normally, and does not require a specific pattern to toggle the override in the sensor.



Is this circuit workable?



                / Wall switch
+------0 0-----+
| |
--Phase-+-----Sensor-----+-------+
| | Lights
--Neutral------+--+--------------+ |
--Earth------------------------------+


The lights are 4x flourescent tubes in two double fittings, but I may add more later. Or may replace with LED fittings if that helps.



Essentially I'm trying to replicate the function of an Occupancy Sensor wall plate, like this:



https://content.interlinebrands.com/product/Image/Detail/10033/106791_usn.jpg



For some reason these aren't available in New Zealand. Voltage is 230 VAC at 50Hz.





The main reasons for concern are that:




  • the sensor will have live voltage on both sides even when the sensor is off.

  • the lights will not be isolated from power simply by turning off the wall switch. Adequate labelling at the lights should cover this
    ("WARNING DUAL SUPPLY! Disable sensor AND check for voltage before servicing.")



Related to but not a dupe of




  • How should dual motion sensors be connected?

  • multiple motion detectors wired together










share|improve this question
























  • Just realised the Neutral line should be joined around the sensor too, else the light won't run when the switch is on.
    – Criggie
    3 hours ago
















1














I wish to have a motion sensor on the lights in my garage, but I also want to have an override switch that works normally, and does not require a specific pattern to toggle the override in the sensor.



Is this circuit workable?



                / Wall switch
+------0 0-----+
| |
--Phase-+-----Sensor-----+-------+
| | Lights
--Neutral------+--+--------------+ |
--Earth------------------------------+


The lights are 4x flourescent tubes in two double fittings, but I may add more later. Or may replace with LED fittings if that helps.



Essentially I'm trying to replicate the function of an Occupancy Sensor wall plate, like this:



https://content.interlinebrands.com/product/Image/Detail/10033/106791_usn.jpg



For some reason these aren't available in New Zealand. Voltage is 230 VAC at 50Hz.





The main reasons for concern are that:




  • the sensor will have live voltage on both sides even when the sensor is off.

  • the lights will not be isolated from power simply by turning off the wall switch. Adequate labelling at the lights should cover this
    ("WARNING DUAL SUPPLY! Disable sensor AND check for voltage before servicing.")



Related to but not a dupe of




  • How should dual motion sensors be connected?

  • multiple motion detectors wired together










share|improve this question
























  • Just realised the Neutral line should be joined around the sensor too, else the light won't run when the switch is on.
    – Criggie
    3 hours ago














1












1








1







I wish to have a motion sensor on the lights in my garage, but I also want to have an override switch that works normally, and does not require a specific pattern to toggle the override in the sensor.



Is this circuit workable?



                / Wall switch
+------0 0-----+
| |
--Phase-+-----Sensor-----+-------+
| | Lights
--Neutral------+--+--------------+ |
--Earth------------------------------+


The lights are 4x flourescent tubes in two double fittings, but I may add more later. Or may replace with LED fittings if that helps.



Essentially I'm trying to replicate the function of an Occupancy Sensor wall plate, like this:



https://content.interlinebrands.com/product/Image/Detail/10033/106791_usn.jpg



For some reason these aren't available in New Zealand. Voltage is 230 VAC at 50Hz.





The main reasons for concern are that:




  • the sensor will have live voltage on both sides even when the sensor is off.

  • the lights will not be isolated from power simply by turning off the wall switch. Adequate labelling at the lights should cover this
    ("WARNING DUAL SUPPLY! Disable sensor AND check for voltage before servicing.")



Related to but not a dupe of




  • How should dual motion sensors be connected?

  • multiple motion detectors wired together










share|improve this question















I wish to have a motion sensor on the lights in my garage, but I also want to have an override switch that works normally, and does not require a specific pattern to toggle the override in the sensor.



Is this circuit workable?



                / Wall switch
+------0 0-----+
| |
--Phase-+-----Sensor-----+-------+
| | Lights
--Neutral------+--+--------------+ |
--Earth------------------------------+


The lights are 4x flourescent tubes in two double fittings, but I may add more later. Or may replace with LED fittings if that helps.



Essentially I'm trying to replicate the function of an Occupancy Sensor wall plate, like this:



https://content.interlinebrands.com/product/Image/Detail/10033/106791_usn.jpg



For some reason these aren't available in New Zealand. Voltage is 230 VAC at 50Hz.





The main reasons for concern are that:




  • the sensor will have live voltage on both sides even when the sensor is off.

  • the lights will not be isolated from power simply by turning off the wall switch. Adequate labelling at the lights should cover this
    ("WARNING DUAL SUPPLY! Disable sensor AND check for voltage before servicing.")



Related to but not a dupe of




  • How should dual motion sensors be connected?

  • multiple motion detectors wired together







electrical wiring switch motion-sensor






share|improve this question















share|improve this question













share|improve this question




share|improve this question








edited 3 hours ago

























asked 4 hours ago









Criggie

777416




777416












  • Just realised the Neutral line should be joined around the sensor too, else the light won't run when the switch is on.
    – Criggie
    3 hours ago


















  • Just realised the Neutral line should be joined around the sensor too, else the light won't run when the switch is on.
    – Criggie
    3 hours ago
















Just realised the Neutral line should be joined around the sensor too, else the light won't run when the switch is on.
– Criggie
3 hours ago




Just realised the Neutral line should be joined around the sensor too, else the light won't run when the switch is on.
– Criggie
3 hours ago










2 Answers
2






active

oldest

votes


















2














As I discuss in the answer you linked, that is fine. There are some minor glitches in your drawing, but nothing worrisome. Try



                / Wall switch
+------0 0-----+
| |
--Phase-+-----Sensor-----+-------+
| Lights
--Neutral--------+---------------+


(ground removed for clarity, actually it's needed at all devices assuming NZ code does not delete this popular requirement). And this is strictly a schematic, the wiring method must be such that currents balance in each cable or conduit.



A quality, modern motion sensor with its own neutral isn't going to have a problem with its LOAD hot being externally hottified by a switch or other motion sensor.



A maintainer, especially one who has looked around the room and observed motion sensors, should be shutting off power at the circuit breaker. I have no sympathy for someone who wants to work the circuit "hot", unless NZ Code has a variation that says I should. For all the servicer knows, it's wired with a switched neutral.






share|improve this answer





























    1














    I've done this. Works great. A switch and motion sensor in parallel. It also works with two motion sensors. Only thing is that highest takes precedence, in other words if the motion sensor turns the light on the switch is not able to turn it off. I tolerate this issue.



    Works great.



    good luck.






    share|improve this answer





















      Your Answer








      StackExchange.ready(function() {
      var channelOptions = {
      tags: "".split(" "),
      id: "73"
      };
      initTagRenderer("".split(" "), "".split(" "), channelOptions);

      StackExchange.using("externalEditor", function() {
      // Have to fire editor after snippets, if snippets enabled
      if (StackExchange.settings.snippets.snippetsEnabled) {
      StackExchange.using("snippets", function() {
      createEditor();
      });
      }
      else {
      createEditor();
      }
      });

      function createEditor() {
      StackExchange.prepareEditor({
      heartbeatType: 'answer',
      autoActivateHeartbeat: false,
      convertImagesToLinks: false,
      noModals: true,
      showLowRepImageUploadWarning: true,
      reputationToPostImages: null,
      bindNavPrevention: true,
      postfix: "",
      imageUploader: {
      brandingHtml: "Powered by u003ca class="icon-imgur-white" href="https://imgur.com/"u003eu003c/au003e",
      contentPolicyHtml: "User contributions licensed under u003ca href="https://creativecommons.org/licenses/by-sa/3.0/"u003ecc by-sa 3.0 with attribution requiredu003c/au003e u003ca href="https://stackoverflow.com/legal/content-policy"u003e(content policy)u003c/au003e",
      allowUrls: true
      },
      noCode: true, onDemand: true,
      discardSelector: ".discard-answer"
      ,immediatelyShowMarkdownHelp:true
      });


      }
      });














      draft saved

      draft discarded


















      StackExchange.ready(
      function () {
      StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f153954%2fmotion-sensor-with-bypass-switch%23new-answer', 'question_page');
      }
      );

      Post as a guest















      Required, but never shown

























      2 Answers
      2






      active

      oldest

      votes








      2 Answers
      2






      active

      oldest

      votes









      active

      oldest

      votes






      active

      oldest

      votes









      2














      As I discuss in the answer you linked, that is fine. There are some minor glitches in your drawing, but nothing worrisome. Try



                      / Wall switch
      +------0 0-----+
      | |
      --Phase-+-----Sensor-----+-------+
      | Lights
      --Neutral--------+---------------+


      (ground removed for clarity, actually it's needed at all devices assuming NZ code does not delete this popular requirement). And this is strictly a schematic, the wiring method must be such that currents balance in each cable or conduit.



      A quality, modern motion sensor with its own neutral isn't going to have a problem with its LOAD hot being externally hottified by a switch or other motion sensor.



      A maintainer, especially one who has looked around the room and observed motion sensors, should be shutting off power at the circuit breaker. I have no sympathy for someone who wants to work the circuit "hot", unless NZ Code has a variation that says I should. For all the servicer knows, it's wired with a switched neutral.






      share|improve this answer


























        2














        As I discuss in the answer you linked, that is fine. There are some minor glitches in your drawing, but nothing worrisome. Try



                        / Wall switch
        +------0 0-----+
        | |
        --Phase-+-----Sensor-----+-------+
        | Lights
        --Neutral--------+---------------+


        (ground removed for clarity, actually it's needed at all devices assuming NZ code does not delete this popular requirement). And this is strictly a schematic, the wiring method must be such that currents balance in each cable or conduit.



        A quality, modern motion sensor with its own neutral isn't going to have a problem with its LOAD hot being externally hottified by a switch or other motion sensor.



        A maintainer, especially one who has looked around the room and observed motion sensors, should be shutting off power at the circuit breaker. I have no sympathy for someone who wants to work the circuit "hot", unless NZ Code has a variation that says I should. For all the servicer knows, it's wired with a switched neutral.






        share|improve this answer
























          2












          2








          2






          As I discuss in the answer you linked, that is fine. There are some minor glitches in your drawing, but nothing worrisome. Try



                          / Wall switch
          +------0 0-----+
          | |
          --Phase-+-----Sensor-----+-------+
          | Lights
          --Neutral--------+---------------+


          (ground removed for clarity, actually it's needed at all devices assuming NZ code does not delete this popular requirement). And this is strictly a schematic, the wiring method must be such that currents balance in each cable or conduit.



          A quality, modern motion sensor with its own neutral isn't going to have a problem with its LOAD hot being externally hottified by a switch or other motion sensor.



          A maintainer, especially one who has looked around the room and observed motion sensors, should be shutting off power at the circuit breaker. I have no sympathy for someone who wants to work the circuit "hot", unless NZ Code has a variation that says I should. For all the servicer knows, it's wired with a switched neutral.






          share|improve this answer












          As I discuss in the answer you linked, that is fine. There are some minor glitches in your drawing, but nothing worrisome. Try



                          / Wall switch
          +------0 0-----+
          | |
          --Phase-+-----Sensor-----+-------+
          | Lights
          --Neutral--------+---------------+


          (ground removed for clarity, actually it's needed at all devices assuming NZ code does not delete this popular requirement). And this is strictly a schematic, the wiring method must be such that currents balance in each cable or conduit.



          A quality, modern motion sensor with its own neutral isn't going to have a problem with its LOAD hot being externally hottified by a switch or other motion sensor.



          A maintainer, especially one who has looked around the room and observed motion sensors, should be shutting off power at the circuit breaker. I have no sympathy for someone who wants to work the circuit "hot", unless NZ Code has a variation that says I should. For all the servicer knows, it's wired with a switched neutral.







          share|improve this answer












          share|improve this answer



          share|improve this answer










          answered 3 hours ago









          Harper

          65.4k342133




          65.4k342133

























              1














              I've done this. Works great. A switch and motion sensor in parallel. It also works with two motion sensors. Only thing is that highest takes precedence, in other words if the motion sensor turns the light on the switch is not able to turn it off. I tolerate this issue.



              Works great.



              good luck.






              share|improve this answer


























                1














                I've done this. Works great. A switch and motion sensor in parallel. It also works with two motion sensors. Only thing is that highest takes precedence, in other words if the motion sensor turns the light on the switch is not able to turn it off. I tolerate this issue.



                Works great.



                good luck.






                share|improve this answer
























                  1












                  1








                  1






                  I've done this. Works great. A switch and motion sensor in parallel. It also works with two motion sensors. Only thing is that highest takes precedence, in other words if the motion sensor turns the light on the switch is not able to turn it off. I tolerate this issue.



                  Works great.



                  good luck.






                  share|improve this answer












                  I've done this. Works great. A switch and motion sensor in parallel. It also works with two motion sensors. Only thing is that highest takes precedence, in other words if the motion sensor turns the light on the switch is not able to turn it off. I tolerate this issue.



                  Works great.



                  good luck.







                  share|improve this answer












                  share|improve this answer



                  share|improve this answer










                  answered 1 hour ago









                  Trout

                  8721917




                  8721917






























                      draft saved

                      draft discarded




















































                      Thanks for contributing an answer to Home Improvement Stack Exchange!


                      • Please be sure to answer the question. Provide details and share your research!

                      But avoid



                      • Asking for help, clarification, or responding to other answers.

                      • Making statements based on opinion; back them up with references or personal experience.


                      To learn more, see our tips on writing great answers.





                      Some of your past answers have not been well-received, and you're in danger of being blocked from answering.


                      Please pay close attention to the following guidance:


                      • Please be sure to answer the question. Provide details and share your research!

                      But avoid



                      • Asking for help, clarification, or responding to other answers.

                      • Making statements based on opinion; back them up with references or personal experience.


                      To learn more, see our tips on writing great answers.




                      draft saved


                      draft discarded














                      StackExchange.ready(
                      function () {
                      StackExchange.openid.initPostLogin('.new-post-login', 'https%3a%2f%2fdiy.stackexchange.com%2fquestions%2f153954%2fmotion-sensor-with-bypass-switch%23new-answer', 'question_page');
                      }
                      );

                      Post as a guest















                      Required, but never shown





















































                      Required, but never shown














                      Required, but never shown












                      Required, but never shown







                      Required, but never shown

































                      Required, but never shown














                      Required, but never shown












                      Required, but never shown







                      Required, but never shown







                      Popular posts from this blog

                      Accessing regular linux commands in Huawei's Dopra Linux

                      Can't connect RFCOMM socket: Host is down

                      Kernel panic - not syncing: Fatal Exception in Interrupt